USFaster Tender
ClosedSmall BusinessCombined Synopsis/Solicitation

FLUID CHILLER

W6QK ACC- DTADEPT OF DEFENSE / DEPT OF THE ARMY / W6QK ACC- DTA

Posted
Jun 17, 2025
Response deadline
Jun 24, 2025, 3:00 PM EDT
Closed
Value
Category
HVAC / Plumbing
NAICS
333413
PSC / Class
4140
Set-aside
Total Small Business Set-Aside (FAR 19.5)
Place of performance
Solicitation #
W912CH25QA017
Archive date
Jun 17, 2026

Search tags

Description

FLUID CHILLER:61,000 BTU?s / Hr Inlet /Outlet Piping needs to be 11/4? NPT. Pump Specifications must be 18 GMP at 38 PSI. Voltage / Phase must be 230/1, 230/3, 460/3Rated load amps at 11A@460/3. Dimensions must be 42?L X 28?W X 66?H. Dry Weight must be approximately 760 lbs. Chiller outlet temp should be 50 degrees Fahrenheit. Must have at least a 26-gallon reservoir. Chiller pump must be rated for no less than 5gpm. Pump must be continuous duty and of stainless-steel construction. All piping must be non-ferrous. Shall have a footprint no larger than 42? x 28? and less than 80? in height. Shall have a digital display for temperature display and control. Shall use R407c refrigerant. Shall have a highly efficient scroll compressor. Shall include at least a 1-year parts and labor warranty. Must be rated to operate outside all year.